The Protocol Converter UNIGATE CL connects devices such as automation components via their serial interfaces to the required fieldbus or industrial Ethernet standard. RS232, RS485 and RS422 interfaces are on Board as a standard feature.
The communication between the serial side and the bus takes place either through the device configuration and a selection of the commercially available protocol, such as Modbus ASCII, Modbus RTU (Master or slave), 3964 (R) (e. g. for RK512) or the device is controlled by a script for protocols such as DIN measuring bus, DIN 19244 or other proprietary protocols.
This Script is created with the free PC tool, ‘Protocol Developer’. You decide whether you want to program the Script yourself or hire Deutschmann Automation to do so.
A special feature of the UNIGATE CL series is Brand labeling. With the customized design Deutschmann Automation not only gives you the opportunity to pre-configure the device and choose different housing colors, you can also apply your own logo.
Data sheet
Dimensions (WxDxH in mm) |
23 x 117 x 111 (screw-plug-connector included) |
---|---|
Weight |
approx. 123 g |
Protection class | IP20 |
Housing material | Polyamid |
Mounting | DINrail (EN 50022) |
Voltage supply | 10 up to 33 Volt DC Protection against incorrect polarity, short circuit and overload integrated |
Current consumption (at +24V/DC) | typ. 50mA, max. 60mA |
Operating temperature | -40°C (not condensing) up to +85°C |
Storage/transport temperate | -40°C ... +85°C |
Fieldbus Function | All specified CANopen Slave functions |
Technology | ASIC |
Certifications | CE |
Galvanic division | Standard on the bus side |
Options | Galvanic division for the application side |
Order designation | Description | Order number |
UNIGATE CL-C4 | DIN-rail module with seral interface - RS232, 422 and 485 on-board - to CANopen. Additional Debug-interface, Housing: sky blue RAL 5015 | V3554 |
---|---|---|
UNIGATE CL-GT-C4 | DIN-rail module with seral interface - RS232, 422 and 485 on-board - to CANopen. Additional Debug-interface, Housing: sky blue RAL 5015. Additional galvanic separation RS-side (RS-Interface) | V3708 |
Optional | Neutral version | on request |
Optional | Customized design | on request |
Note: Further variants can be found in the brochure and the price list. |